So as part of a new network deployment which mandated that the X-Serve (Dual Ghz Intel (2 X 2cores) and X-Serve (7TB) be in the same room as clients, we purchased an XRackPro2 6U. We have installed a Gigabit Switch, Fiber Switch, Xserve, and XServe Raid. We're noticing that the temps with the door closed are 10 degrees warmer than with the door open.
Door Close Left Inlet 84 Degree F Right Inlet 77 Degree F
And the fans are 8200 In and 4800 Out Across the CPUS
With the door closed the Inlet temp jumps to 95 and Fans to 12000 and this is with the server under NO load.
What are other users of this rack seeing? The room is climate controlled to 72 degrees F.
Imported from the Apple Support Forums via the Wayback Machine 🔗
You specified two 'Door Closed' measurements - do you mean your Door Open temps are 84° and 77° and door closed temp is 95°?
If so that clearly indicates a problem. 95° is way too close to the maximum operating temperature, and if the server is idle at that time then you're going to go over when it gets busy.
What it indicates to me is that you have a circulation problem - hot air isn't getting exhausted out of the enclosure and is cycling to the front of the enclosure where it's getting re-heated again.
I've not used the 6U, but I have used other XRack Pros, so am hoping the setup is similar...
You have powered on the fans on the rear door, right? These are going to be essential, even if it decreases the sound dampening effect.
IIRC there are also vents in the bottom panel at the front which will increase the amount of cool air entering the enclosure.
0
Apple Support Community member·
Imported from the Apple Support Forums via the Wayback Machine 🔗
yep those measurements of 84/77 are with the door open, and the 95 is with the door closed. The ambient in the room is 70.
The fans in the back are plugged in and running. Doing well to take out the heat. Whats fascinating is when I peg the CPU's encoding, the fans increase to about 15k, and the temps stay stable.
The unit has filter and grate on the bottom for the air to come in, but I think the cutout is too small. As I look online at the other units it looks like the cutout for the filters is HUGE, and the entire floor is basically a vent. On this one its just a small area in the front.
Will call them. The issue is this type of equipment is a ***** to ship back, but something clearly isnt working well.
Camelot, are you seeing temp differences like this?
0
Apple Support Community member·
Imported from the Apple Support Forums via the Wayback Machine 🔗
How close are the front of the Xserves to the door? The airflow of the Xserves is front to back so you need some clearance in front of them or you can get a "dead spot" where air flows around the unit but not to the front of the Xserve. I think the high inlet temperature is a sign that the air is circulating around inside the unit rather than getting good in-out flow.
If you have removed the extra insulation so the unit is as open as it can be and the Xserves are at the same level as the exhaust fans I'm not sure what else there is to do. Some people advocate filling any empty slots with the 1U blank faces to restrict clear front to back flow except through the servers but I'm not sure how much I believe that really helps.
I have used both of the bigger units (12 and 24U) cases and they do run cooler with the door open but they shouldn't vary that much. One other warning - don't leave the back open with the front closed for any amount of time because opening the back moves the exhaust fans away while the front flow is still constricted.
My $.02,
=Tod
0
Apple Support Community member·
Imported from the Apple Support Forums via the Wayback Machine 🔗
Hey Tod,
When you say extra insulation, what are you speaking off. the padding on the side and bottom?? THe units are mounted at the default depth. Leaving about 2 inches or so of clearance in the front of the units. But there really isnt much room to move them more rearward. as it is about hitting the back door. And fans are level with XServe exhaust. And in my case all the blank slots are filled with gear, so that should be helping.
I wonder if this small case just isn't well vented... Been reaching out to Gizmac to see what they have to say, will report back.
0
Apple Support Community member·
Imported from the Apple Support Forums via the Wayback Machine 🔗
It sounds as if the XServe fans are moving more volume of air than the enclosure fans can exhaust, thus recirculating already heated air back through the units. It will be interesting to see what the manufacturer of the rack has to say.
0
Apple Support Community member·
Imported from the Apple Support Forums via the Wayback Machine 🔗
We're working through it now. Will report back what they say. They have been great thus far.